The GF302D3 portable three phase electric meter test bench consists of an integrated three phase 20A current source and 500V voltage source and a class 0.05 three phase electronic reference standard meter.
The electric meter test bench is particularly designed for analysis of complete metering installations and local mains conditions. The meter test bench offers high functionality combined with an excellent menu guided operation via built-in thirty keys and colored 7” touch LCD-display.Electrical parameters | |
---|---|
Accuracy | 0.02%, 0.05%, 0.1% |
Power Supply | Single phase AC 85-265V, frequency 50/60Hz. |
AC Voltage Output | |
Range(U1,U2,U3) | 57.7V, 100V, 220V, 380V or 69.3V, 120V, 240V, 480V( optional); max 500V |
Adjustment range | (0-120)%RG(1) |
Adjustment fineness | 0.01%RG, 0.1%RG, 1%RG, 10%RG as optional. |
Stability | 0.01%/120s |
Distortion | 0.2% (Non-capacitive load) |
Output load | each phase 25VA |
Accuracy | 0.05%RG or 0.02%RG |
AC Current Output | |
Range(I1,I2,I3) | 200mA, 1A, 5A, 20A; max 25A |
Adjustment range | (0-120)%RG |
Adjustment fineness | 0.01%RG, 0.1%RG, 1%RG, 10%RG as optional. |
Stability | <0.01%/120s |
Distortion | ≤0.2% (Non-capacitive load) |
Output load | 25VA |
Accuracy | 0.05%RG or 0.02%RG |
Power Output | |
Active power output stability | <0.01%RG/120s |
Reactive power output stability | <0.02%RG/120s |
Active power measuring accuracy | 0.05%RG or 0.02%RG |
Reactive power measuring accuracy | 0.1%RG |
Phase Output | |
Output adjustment range | 0°-359.999° |
Output adjustment fineness | 10, 1, 0.1, 0.01 as optional. |
Resolution | 0.01° |
Accuracy | 0.02° |
Power Factor | |
Adjustment range | -1 ~ 0 ~ 1 |
Resolution | 0.0001 |
Measurement accuracy | 0. 0005 |
Frequency Output | |
Adjustment range | 40Hz-70Hz |
Output adjustment fineness | 5Hz, 1Hz, 0.1Hz, 0.01Hz as optional. |
Resolution | 0.001Hz |
Accuracy | 0.002Hz |
Voltage /Current/Harmonic Setting Output | |
Harmonic number | 2-51times |
Harmonic content | 0-40% |
Harmonic phase | 0-359.99 |
Harmonic setting accuracy | (10%±0.1%)RD(2) |
Power Energy Measurement Error | |
Active power energy | 0.05%RG or 0.02%RG |
Reactive power energy | 0.1%RG |
Power Pulse Output | |
Power pulse type | active pulse, reactive pulse |
Active power pulse output | 5V, 10mA |
Power Pulse Input | |
Energy pulse type | support active and reactive pulse, the highest frequency power pulse input is 180K. |
Communication Port | |
Communication Port | RS232, USB2.0 |
Safety | |
Isolation protection | IEC 61010-1:2001 |
Measurement Category | 300 V CAT III, 600 V CAT II |
Degree of protection | IP20 |
Declaration of conformity | CE certified |
Mechanical parameters | |
Dimensions (W×D×H) (mm) | 445x460x158 |
Weight (kg) | 18 |
(1) RG means range, the same as below; (2) RD means the setted harmonic content, harmonic can be a single output, also multiple output. |
Beijing GFUVE Instrument Transformer Manufacturer Co.,Ltd.
Beijing GFUVE Instrument Transformer Manufacturer Co., Ltd. was established in 2008. It combined design, manufacturing and sales together as one high-tech enterprise. GFUVE Instrument Transformer company mainly produces less than 35kV current transformer and voltage transformer, split core ct and current clamp models etc.
GFUVE is a leader manufacturer of split core current transformer products in China. It is professional in current transformer, potential transformer and related accessory. The product of outdoor split core current transformer develops very quickly in the global market. Our company has achieved certification to ISO9001. The products are sold to over 30 provinces in China and exported to overseas including South America, Middle East, Southeast Asia, Australia and Africa.